Updating Cart...
  • Free transportation to the installation site
  • Free initial installation and setup
  • 2-year official warranty and 10 years of after-sales service
ZM R online single phase to single phase transformer-less UPS

The ZM R UPS series, available in power ratings from 1 to 3 kVA, is an Online Double Conversion uninterruptible power supply designed to protect sensitive IT equipment, computer networks, security systems, laboratory equipment and other critical loads. With a unity output power factor (kW = kVA), ZM R enables full utilization of the UPS rated capacity, making it an ideal solution for modern high-density loads. Its flexible Rack/Tower convertible design, combined with a rotatable LCD display, allows installation either as a tower unit or inside a standard rack enclosure. Internal batteries provide reliable backup time, while the Hot-Swap battery feature enables battery replacement without shutting down the UPS or interrupting power to connected equipment. Advanced digital control, wide input voltage range, intelligent battery charging and smart fan speed regulation improve system reliability and extend component lifetime. The LCD display provides real-time information including input and output status, load level, battery capacity and alarm notifications. Equipped with USB and RS232 communication ports together with an intelligent communication slot, ZM R offers comprehensive monitoring and remote management capabilities. ZM R is a reliable and cost-effective power protection solution for small data centers, network racks and professional applications.

Read more...
Topology
Online Double Conversion
Power Range
1 - 3 kVA
Input / Output
1P : 1P (in:out)
Output Power Factor
P.F. = 1
Features:

Unity output power factor (kW = kVA)

Rack/Tower convertible design

Hot-Swap battery capability

Wide input voltage range

LCD display

Communication slot available

Whats in the packing:
user manual iconUser Manual
usb cableUSB Cable
rs232 serial cableRS232 Serial Cable
rack mount kitRackmount Kit

Ask me!

4.1 ★
  • Performance
  • Reliability
  • Features
  • Build Quality
  • Value for Money
(AI Generated)
* Power:
- +
 Purchase Steps

 Purchase Steps

 Product Originality

 Product Originality

UPS/Model
Select Model
UPS/Input
Nominal Voltage
200/208/220/230/240 Vac (single phase + N)
Voltage Range
110 to 300 Vac @ max 50% load (single phase), 176 to 300 Vac @ max 100% load (single phase); (tolerance ±5%)
Frequency Range
rated: 50 or 60 Hz (automatic select), range: 40 to 70 Hz
Power Factor
0.99 at 100% load (nominal input voltage)
Inlet Type
- select a model from top -
UPS/Bypass
Voltage Range
176 to 264 Vac (can be set via lcd display)
Frequency Range
Derate to 75% of capacity when the Input voltage frequency out of range(50 or 60 Hz ±4 Hz)
UPS/Output
Power
- select a model from top -
Nominal Voltage
200/208/220/230/240 Vac (single phase + N)
Voltage Variation
static variation ±1%
Frequency Range
50 or 60 Hz (tolerance ±0.1٪)
Power Factor
1
Voltage Distortion (THDv)
≤ 1% with resistive linear load, ≤ 5% with non-linear load
Outlet Type
- select a model from top -
Wave form
pure sinewave
Efficiency
- select a model from top -
UPS/Battery
Battery Type
only internal battery
Qty × Voltage
- select a model from top -
Recharging Time
4 hours to 90% after complete discharge
UPS/Protections
Overload
AC mode: 105% < load ≤ 125% for 1 min then transfer to bypass, 125% < load ≤ 130% for 30 sec then transfer to bypass, over 130% transfer to bypass immediately Battery mode: 105% < load ≤ 125% for 1 min, 125% < load ≤ 130% for 10 sec, over 130% shut down immediately
Protections
over-current, short-circuit, over-voltage, under-voltage, over-temperature, excessive low battery
Alarms
line failure, battery low, over-load, fault conditions
UPS/Physical
Dimensions (W × D × H)
- select a model from top -
Weight
- select a model from top -
UPS/Environment
Working Temperature
ambient: min 0 °C, max 40 °C, recommended for battery life: 20 to 25 °C
Working Humidity
max 95% non-condensing
Noise Level
max 50 dBA @ 1 m
UPS/Others
Communications
USB type B, RS232, slot for communications interface
Standards
Safety: IEC/EN 62040-1, IEC/EN 62477-1 EMC: IEC/EN 62040-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8
Other Specifications
Transfer time: zero (ac <-> batt), 4 ms typical (inv <-> byp)

What is the advantage of unity output power factor in ZM R?
The unity output power factor allows full utilization of the UPS rated capacity. This feature enables modern IT equipment and servers to operate without reducing the available output capacity, making the UPS suitable for high-density loads.
What information is displayed on the LCD screen?
The LCD display provides real-time information including input and output voltage, load level, battery capacity, operating status and alarm notifications, simplifying system monitoring and management.