Multi Power 2 online three phase to three phase modular UPS

The Multi Power 2 UPS, an advanced generation of modular UPS systems, features 67 kW power modules, delivering an exceptional 98.1% efficiency in online mode, an output power factor of 1, and input harmonic distortion below 2.5%, making it ideal for computer networks and data centers. The use of Silicon Carbide (SiC) technology in the Blue series power modules reduces energy and heat losses, minimizing the need for energy-intensive cooling systems and providing a reliable and sustainable solution. The Smart Modular Architecture (SMA) in the Multi Power 2 automatically monitors module health and synchronizes the firmware of connected modules. The hot-swap capability of the modules enables seamless power expansion, while the efficiency control system optimizes performance and redundancy by intelligently activating the required number of modules. Its wide input voltage acceptance range (up to 40% below nominal voltage at half load) keeps the rectifier active, preventing battery switching; the system maintains operation without battery use even during a single-phase outage (up to 66% load) or a two-phase outage (up to 33% load). The Power Walk-in feature in the rectifier gradually ramps up the input current, preventing sudden stress on input sources and ensuring more stable performance. The Multi Power 2 supports a variable number of batteries (30 to 44); with 30 batteries, 75% of the capacity is usable, and with 40 batteries, the full UPS capacity is available. Configurations such as PCM (frame with internal manual bypass for 500 kVA device), PC0 (without switches), and PCS (with input/output/bypass/manual bypass switch sets) enhance installation flexibility. The 7-inch touchscreen display graphically presents the UPS parameters and operating status. Parallel scalability up to 2400 kW (4 systems) provides maximum capacity. The Multi Power 2, with its focus on environmental sustainability and reduced energy waste, ensures a reliable future for digital infrastructure.

Read more...
Topology
Modular Online
Power Range
300 - 600 kVA
Input/Output
3P : 3P (in:out)
Output Power Factor
P.F. = 1
Features:

Minimal space requirement

Output power factor of 1

Very high efficiency

High flexibility and scalability

Color LCD display with touchscreen capability

Exceptional reliability

Whats in the packing:
user manual iconUser Manual
usb cableUSB Cable
front access keyFront Door Access Key
hookHook for Device Transportation

Ask Me!

4.9 ★
  • Performance
  • Reliability
  • Features
  • Build Quality
  • Value for Price
(Generated by AI)
* Model:
* Power module qty.:
* Required backup time:
Other:
- +
 Purchase Steps

 Purchase Steps

 Product Originality

 Product Originality

UPS/Model
Select Model
UPS/Input
Nominal Voltage
380, 400, 415 VAC three-phase + N
Voltage Range
240 to 480 VAC @ 50% load, 340 to 480 VAC @ 100% load
Frequency Range
40 to 72 Hz
Power Factor
0.99
Voltage Distortion (THDi)
< 3%
Inlet Type
terminal
UPS/Bypass
Voltage Range
from 180 VAC (adjustable 180 to 200 VAC) to 264 VAC (adjustable 250 to 264 VAC) referring to Neutral
Frequency Range
50 or 60 Hz, tolerance ±5% (selectable)
UPS/Output
Power
- select a model from top -
Nominal Voltage
380, 400, 415 VAC three-phase + N (selectable)
Voltage Variation
static variation ±1%, dynamic variation EN62040-3 class performance 1 non-linear load
Frequency Range
50 or 60 Hz (selectable)
Power Factor
1
Voltage Distortion (THDv)
< 1.5% with linear load, < 2.5% with non-linear load
Outlet Type
terminal
Wave form
sinusoidal
Efficiency
- select a model from top -
UPS/Battery
Battery Type
external
Qty × Voltage
nominal: 40 × 12 = 480 VDC, variable: min 30 pcs (75% of UPS power available), max 44 pcs
UPS/Protections
Overload
125% for 10 min; 150% for 1 min
Protections
over-current, short-circuit, over-voltage, under-voltage, over-temperature, excessive low battery
Alarms
line failure, battery low, over-load, fault conditions
UPS/Physical
Dimensions (W × D × H)
- select a model from top -
Weight
- select a model from top -
UPS/Environment
Working Temperature
ambient: min 0 °C, max 40 °C, recommended for battery life: 20 to 25 °C
Working Humidity
max 95% non-condensing
Altitude Level
1000 m @ nominal power (Derating 1% power for every 100 m above 1000 m, max 6000 m)
Noise Level
- select a model from top -
UPS/Others
Communications
2 × RS232 + dry contacts + 2 slots for communications interface
Standards
European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 - category C2; RoHS compliant Classification in accordance with IEC 62040-3 (Voltage Frequency Indipendent) VFI - SS - 111
Other Specifications
PCM: with manual bypass switch, including full power module
PC0: without switches, including full power module
PCS: with input, bypass, output, manual bypass switches, including full power module

What is the maximum power capacity of the Multi Power 2 UPS?
The Multi Power 2 UPS offers a scalable power range from 300 kVA to 1,600 kVA in a single unit. When configured in parallel, up to four systems can operate together, providing a total capacity of up to 6,400 kVA. This scalability ensures that the system can grow with your power requirements.
Can the Multi Power 2 UPS operate in high ambient temperatures?
Yes, the Multi Power 2 is designed to operate in ambient temperatures up to 40°C without derating. This capability reduces the need for extensive cooling systems, leading to cost savings and increased reliability in various environments.
Home Products Downloads Call Now Your Quote